By: Khanda Sharif Khanda Sharif, Michael Gormley, Michael Gormley
The performance of a building drainage system, “BDS”, is determined by the complexity of internal airflow and pressure dynamics, governed by unsteady wastewater flows from randomly discharging appliances such as WCs, sinks, and baths. Designers attempt to optimise system safety by equalising pressure and incorporating ventilation pipes and active devices such as AAVs and positive pressure reduction devices (PPRDs). However, failures within these systems can lead to foul gases and potentially hazardous microbes entering habitable spaces and posing a risk to public health. This study, for the first time, develops a novel model that simulates the effect of air from the sewer on BDS performance, which describes the correlation between system airflow and air pressure under the influence of air from the sewer. A combination of full-scale laboratory experiments representing a 3-storey building and real-world data from a 32-storey test rig configured as a building demonstrated that sewer air significantly modifies airflow and air pressure within a BDS. These findings are crucial for modern urban environments, where the prevalence of tall buildings amplifies the risks associated with air pressure transients. This work paves the way for updating codes to more effectively address real-world challenges.